Laureate™
Modbus or Laurel ASCII Protocol
Serial Output DIN Rail Transmitters

DIN
Rail mounted, digitally programmable.
Exceptional accuracy at high update rates.
|
|
Features |
Selectable Modbus or Laurel ASCII protocol. |
Modbus
RTU or ASCII modes, 2-wire connection, up to 247 digital
addresses. |
Output
accuracy: ±0.01% of span for DC signals (±0.1% for AC
rms). |
Output
update rate to 50 or 60/sec. |
95-240V
AC power standard. |
Low
voltage AC or DC power optional. |
Built-in
5V, 10V or 15V dc excitation output. |
Mountable
on 35 mm DIN rail. |
Only
22.5 mm thick. |
Detachable
screw clamp connectors. |
Easy
setup using Laurel's PC-based Instrument Setup Software.
|
Optional
isolated scalable analog output (4-20 mA or 0-10V).
|
Optional
dual solid state relays for alarm or control.
|
Optional
custom curve linearization (Extended main board).
|
|
|
Serial
Output Transmitters by Input Signal
Click on
the links below for transmitter descriptions and specifications
by signal type. Each of the Laureate transmitters listed also
has a Laureate digital panel meter counterpart with the same
signal conditioner.
Analog Input
Transmitters, Modbus or Laurel ASCII I/O:
Pulse Input Transmitters,
Modbus or Laurel ASCII I/O:
Serial Input (Modbus or Laurel
ASCII), Analog Output Transmitter:
|
|
Description
Laureate TM Series
serial output transmitters can be
jumpered for two signal levels: RS232 or RS485. Two serial protocols
are selectable in software: Modbus or Laurel's Custom ASCII.
- Modbus protocol operation
is fully compliant with the Modbus Over Serial Line Specification
V1.0 (2002) for 2-wire, half-duplex connection. This includes
RTU or ASCII modes, addressing of up to 32 devices per RS485
line without a repeater, and up to 247 digital addresses.
Modbus operation allows devices by different manufacturers
to be connected in parallel and be addressed using the same
protocol.
- Laurel’s
Laurel ASCII protocol allows
up to 31 Laureate devices to be addressed on the same RS485
data line. It is simpler than the Modbus protocol and is
recommended when all devices are Laureates. It also allows
use of Laurel’s datalogging software.
Laureate
transmitters are housed in a 35 mm DIN rail case that is only
22.5 mm (0.89") thick. Signal connections are via detachable
screw terminal connectors. The transmitters duplicate the
performance and extensive programmable features of their Laureate
digital panel meter, counter and timer counterparts. Features
include exceptional accuracy at high read rate.
For DC input signals (DC, process,
load cell, strain, potentiometer follower), output accuracy
is ±0.01% of full scale input, as provided by the 16-bit analog-to-digital
converter front end. Full conversion accuracy is maintained
in the Modbus output. Advanced standard features made possible
by Modbus operation include peak capture and latched relay
operation, with Reset provided by external or digital commands.
Options
include dual solid state relays for local
alarm or control and an isolated 4-20 mA or 10V (selectable)
analog output, effectively providing a linearized analog transmitter
output that tracks the reading that would be transmitted digitally.
The analog output provides 12-bit (4096 step) resolution of
the output span and is ultra-linear to within one bit. Its
accuracy is ±0.05% of span for all signal types, except for
AC rms, where accuracy is ±0.1%. Output isolation from signal
and power grounds is provided by a separate on-board power
supply, which can drive 20 mA into a 500 ohm load for 10V
compliance. Output isolation eliminates problems caused by
ground loops.
Transmitter programming
is via the unit's serial port using Laurel's
PC-based Instrument
Setup Software. This software can be downloaded from this
website at no charge. The required transmitter-to-PC interface
cable is available from Laurel (P/N CBL03). Laurel's serial
output transmitters and meters can also be part of PC-based
data logging systems using Laurel's Datalogging
Software, which operates under the Laurel ASCII Protocol.
A single software command switches between the Modbus and
Laurel ASCII protocols.
|
|
General Specifications
Modbus Laureate Transmitters
(Click on links in previous section for details
by signal type)
|
Serial I/O (standard) |
| Signal
levels
Data Rates
Output Isolation
Serial Protocols
Devices on RS-485 Line
Modbus Addresses
Modbus Modes
Modbus Compliance |
RS485
(default) or RS232 (jumper selectable)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test.
Modbus RTU, Modbus ASCII, Laurel ASCII (selectable)
32 max without a repeater.
247 max
RTU or ASCII, 2-wire.
Modbus over Serial Line Specification V1.0 (2002). |
|
Transducer Excitation Output
(standard) |
| Jumper
Selection 1
Jumper Selection 2
Jumper Selection 3 |
10V
@ 60 mA, isolated to 50V from signal ground
5V @ 50 mA, isolated to 50V from signal ground
15V @ 60 mA, non-isolated |
|
Dual Relay Output
(optional) |
Relay
Type
Load rating |
Two
solid state relays, SPST, normally open, Form A
120 mA at 130 Vac or 170 Vdc, 28 ohms series resistance. |
|
Analog Output
(optional) |
| Output
Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation |
0-20
mA, 4-20 mA or 0-10 Vdc (selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load )
12 bits (4,096 steps)
±0.05% of output span
250V rms working, 2.3 kV rms per 1 minute test |
| Power
Input |
| Standard
power
Low power option
Frequency
Power Isolation |
95-240V
AC ±10% or 90-300V DC
12-30V AC or 10-48V DC
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test. |
| Mechanical |
Case
Dimensions
Case Mounting
Electrical Connections |
120
x 101 x 22.5 mm.
35 mm rail per DIN EN 50022.
Detachable screw terminal connectors. |
| Environmental |
Operating
Temperature
Storage Temperature.
Relative Humidity |
0°C
to 70°C.
-40°C to 85°C.
95% at 40°C, non-condensing. |
|
|
|
|