Laurel Electronics
provides digital panel meters / controllers, totalizers, counters,
loop-powered meters, temperature meters, for all types of
transducers or process indication & control. |
|
|
|
|
|
|
DC Voltage or
Current Input Modbus or
Laurel ASCII Protocol Serial I/O Transmitter |

|

DIN
Rail mounted, digitally programmable. Exceptional accuracy at high update rates.
|
Click
to Order DC Voltage or Current Input
Transmitter
|
|
Features |
Selectable Modbus or Laurel ASCII protocol. |
Modbus
RTU or ASCII modes, 2-wire connection, up to 247 digital
addresses. |
Output
accuracy: ±0.01% of span for DC signals (±0.1% for AC
rms). |
Output
update rate to 50 or 60/sec. |
Easy
setup using Laurel's PC-based Instrument Setup Software.
|
Optional
isolated scalable analog output (4-20 mA or 0-10V).
|
Optional
dual solid state relays for alarm or control.
|
Optional
custom curve linearization (Extended main board).
|
0.2,
2, 20, 200, 300V & 600V input ranges |
2,
20, 200 mA and 5A input ranges. |
All
ranges factory calibrated. |
Output
accuracy: ±0.01% of full scale input. |
Peak
capture. |
|
|
|
Description
|
|
DC
Ranges. Laureate TM Series, DC input transmitters
provide six voltage ranges and four current ranges,
all factory calibrated and jumper selectable. The
200.00 mV and 2.0000 V ranges provide a high input
impedance of 1 Gohm to minimize the load on the
voltage signal. A 5.000A range measures the IR drop
across a built-in 10 mW current shunt. The transmitters
can also easily be scaled in software for use with
external shunts.
Serial
Data Output. Laureate TM Series transmitters send
data as a serial digital signal. RS485 or RS232
signal levels are jumper selectable and can each
be associated with either the Modbus protocol or
Laurel’s simpler Custom ASCII protocol.
Transmitter
programming is via the unit's three-terminal serial
port using Laurel's PC-based Instrument
Setup Software. This software can be downloaded
from this website at no charge. The required transmitter-to-PC
interface cable is available from Laurel (P/N CBL03).
Laurel's serial output transmitters and meters can
also be part of PC-based data logging sy
stems
using Laurel's Datalogging
Software, which operates under the Laurel ASCII
Protocol. A single software command switches between
the Modbus and Laurel ASCII Protocols.
Transmitter
options include dual solid state relays for local
alarm or control and an isolated 4-20 mA or 10V
(selectable) analog output, effectively providing
a linearized analog transmitter output that tracks
the reading that would be transmitted digitally.
The analog output provides 12-bit (4096 step) resolution
of the output span and is ultra-linear to within
one bit. Its accuracy is ±0.05% of span for all
signal types, except for AC rms, where accuracy
is ±0.1%. Output isolation from signal and power
grounds is provided by a separate on-board power
supply, which can drive 20 mA into a 500 ohm load
for 10V compliance. Output isolation eliminates
problems caused by ground loops.
DIN
Rail Mounting. Laureate transmitters are housed
in a 35 mm DIN rail case that is only 22.5 mm (0.89")
thick. Signal connections are via detachable screw
clamp plug connectors.
|
|
Click
to Order DC Voltage or Current Input
Transmitter
|
|
General Specifications
Modbus Laureate Transmitters
(Click on links in previous section
for details by signal type) |
| Analog
Input |
Range
|
Resolution
|
Input
Ohms
|
DC
Voltage
|
200.00 mV
2.0000 V
20.000 V
200.00 V
600.0 V |
10 µV
100 µV
1 mV
10 mV
100 mV |
1 Gohm
1 Gohm
1 Mohm
1 Mohm
1 Mohm |
DC
Current
|
2.0000 mA
20.000 mA,
200.00 mA
5.000 A |
0.1 µA
1 µA
10 µA
1 mA |
100 ohms
10 ohms
1 ohm
0.01 ohm |
|
Input Resolution
Input Accuracy
Output Update Rate, Max
Max applied voltage
Over-current protection |
16 bits (65,536
steps)
±0.01% of full scale input (determined by ADC).
50/sec at 50 Hz, 60/sec at 60 Hz.
600 Vac for 20, 200 & 600 V ranges, 125 Vac other
ranges.
25x for 2 mA, 8x for 20 mA, 2.5x for 200 mA, 1x for
5 A. |
| Serial
I/O (standard) |
| Signal
levels
Data Rates
Output Isolation
Serial Protocols
Devices on RS-485 Line
Modbus Addresses
Modbus Modes
Modbus Compliance |
RS485
(default) or RS232 (jumper selectable)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test.
Modbus RTU, Modbus ASCII, Laurel ASCII (selectable)
32 max without a repeater.
247 max
RTU or ASCII, 2-wire.
Modbus over Serial Line Specification V1.0 (2002). |
| Transducer
Excitation Output (standard) |
| Jumper
Selection 1
Jumper Selection 2
Jumper Selection 3 |
10V
@ 60 mA, isolated to 50V from signal ground
5V @ 50 mA, isolated to 50V from signal ground
15V @ 60 mA, non-isolated |
|
Dual Relay Output
(optional) |
|
Relay
Type
Load rating |
Two
solid state relays, SPST, normally open, Form A
120 mA at 130 Vac or 170 Vdc, 28 ohms series resistance. |
|
Analog Output
(optional) |
|
Output
Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation |
0-20
mA, 4-20 mA or 0-10 Vdc (selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load )
12 bits (4,096 steps)
±0.05% of output span
250V rms working, 2.3 kV rms per 1 minute test |
| Power
Input |
|
Standard
power
Low power option
Frequency
Power Isolation |
95-240V
AC ±10% or 90-300V DC
12-30V AC or 10-48V DC
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test. |
| Mechanical |
|
Case
Dimensions
Case Mounting
Electrical Connections |
120
x 101 x 22.5 mm.
35 mm rail per DIN EN 50022.
Detachable screw terminal connectors. |
| Environmental |
|
Operating
Temperature
Storage Temperature.
Relative Humidity |
0°C
to 70°C.
-40°C to 85°C.
95% at 40°C, non-condensing. |
|
|
|
|
FLW,