Laurel Electronics
provides digital panel meters / controllers, totalizers, counters,
loop-powered meters, temperature meters, for all types of
transducers or process indication & control. |
|
|
|
|
True
AC RMS Voltage or Current Modbus or Laurel ASCII Protocol
Serial I/O Transmitter
|

|

DIN
Rail mounted, digitally programmable. Exceptional accuracy at high update rates.
|
Click
to Order DC Voltage or Current Input
Transmitter
|
|
Features |
Selectable Modbus or Laurel ASCII protocol. |
Modbus
RTU or ASCII modes, 2-wire connection, up to 247 digital
addresses. |
Output
accuracy: ±0.01% of span for DC signals (±0.1% for AC
rms). |
Output
update rate to 50 or 60/sec. |
Easy
setup using Laurel's PC-based Instrument Setup Software.
|
Optional
isolated scalable analog output (4-20 mA or 0-10V).
|
Optional
dual solid state relays for alarm or control.
|
Optional
custom curve linearization (Extended main board).
|
0.2,
2, 20, 200, 300V & 600V input ranges |
2,
20, 200 mA and 5A input ranges. |
All
ranges factory calibrated. |
Output
accuracy: ±0.01% of full scale input. |
Peak
capture. |
AC
coupled, frequencies from 10 Hz to 10 kHz. |
|
|
Description
|
|
AC
Ranges. The
Laureate Serial I/O, AC RMS input transmitter provides
six voltage ranges and four current ranges, all
factory calibrated and jumper selectable. The 200.00
mV and 2.0000 V ranges provide a high input impedance
of 22 Mohm to minimize the load on the voltage signal.
A special 5.000A range allows the output of 5A current
transformers to be applied directly to the transmitter,
with no need for a stepdown transformer. The current
readings can easily be scaled digitally as needed.
True
RMS. Precision circuitry is used to determine
the root-mean-square of complex waveforms from 10
Hz to 10 kHz. Spikes up to 2.4 times the maximum
of each range are accurately measured. This provides
a crest factor (Vp / Vrms) of 240 for a signal amplitude
of 1% of full scale, decreasing to 2.4 at 100% of
full scale. Laureate AC RMS input transmitters duplicate
the performance and programmable features of their
Laureate AC
RMS digital panel meter counterparts.
High
Accuracy
Maximum
error as a function of frequency
and signal amplitude
|
The
typical accuracy is 99.9% of full scale, decreasing
to 99.8% for low frequency at high amplitude,
or high frequency at low amplitude. The above
graph shows that maximum error is 0.1% of full
scale over all frequency ranges of interest to
AC power measurement. Error increases to 0.2%,
represented by the two shaded areas, at low frequency
and high amplitude, or high frequency and low
amplitude.
Crest
factor increases in inverse proportion to signal
amplitude. As shown on the same graph, the maximum
crest factor (Vp / Vrms) is 2.4x at full-scale
amplitude, increasing to 240 at 1% of full-scale
amplitude.
The
Laureate RMS meter utilizes the same high-speed
analog-to-digital conversion method as all other
Laureate panel meters. However, the meter settling
time and control response to a step change in
AC amplitude are limited by the RMS converter
circuit to approximately 1 second.
Interface
Options
Built-in
Flexibility & Safety
Laureates
may be powered from 95-240
Vac ±10% or 90-300 Vdc, or optionally from
12-30
Vac or 10-48 Vdc. They are available with
red or green LEDs. They are housed in a 1/8
DIN case that meets NEMA 4X (IP65) specifications
from the front when panel mounted. Any setup functions
and front panel keys may be locked out for simplified
usage and security.
|
|
Click
to Order DC Voltage or Current Input
Transmitter
|
|
General
Specifications
|
|
AC Voltage Range |
Resolution |
Input Ohms |
Typ Error at 25°C
10 Hz to 10 kHz |
200.00 mV
2.000 V
20.000 V
200.00 V
600.0 V *
300.0 V |
10 µV
100 µV
1 mV
10 mV
100 mV
100 mV |
22 M
22 M
1 M
1 M
1 M
1 M |
0.15% FS
0.15% FS
0.15% FS
0.15% FS
0.15% FS
0.15% FS |
|
AC
Current (1% to 100% of full scale) |
|
AC Current Range |
Resolution |
Input Ohms |
Typ Error at 25°C
10 Hz to 10 kHz |
|
2.0000 mA
20.000 mA
200.00 mA
5.000 A |
0.1 µA
1.0 µA
10 µA
1.0 mA |
100
10
1
0.01 |
0.15% FS
0.15% FS
0.15% FS
0.25% FS |
| Display |
Readout
Range
Indicators |
5
LED digits, 7-segment, 14.2 mm (.56"),
red or green
-99999 to 99999 or -99990 to 99990
(count by 10 with rounding)
2 red LED lamps |
Accuracy |
Span
Tempco
Zero Tempco
Crest Factor |
0.005%
of reading/°C
0.1 count/°C
2.4x at 100% of full scale |
Response
Time |
RMS
to DC
A-to-D rate
Output Update
Display Update |
1
s conversion settling time
60/s at 60 Hz, 50/s at 50 Hz
56/s at 60 Hz, 47/s at 50 Hz
3.5/s at 60 Hz, 3/s at 50 Hz |
Maximum
Signal |
Max
applied voltage
Over-current protection |
600
Vac for 20, 200, 600V ranges, 125 Vac other
ranges
25x for 2 mA, 8x for 20 mA, 2.5x for
200 mA, 1x for 5 A |
Power |
Voltage,
standard
Voltage, optional
Frequency
Power Isolation |
95-240
Vac ±10% or 90-300 Vdc
12-30 Vac or 10-48 Vdc
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test |
Excitation
Output
(standard) |
5
Vdc
10 Vdc
24 Vdc
Output isolation |
5
Vdc ±5%, 100 mA
10 Vdc ±5%, 120 mA
24 Vdc ±5%, 50 mA
50 Vdc to meter ground |
Analog
Output (optional) |
Output
levels
Compliance
Scaling
Resolution
Isolation |
0-10V,
0-20 mA, 4-20 mA (jumper selectable)
2 mA at 10V (5 kOhm load), 12V at 20 mA (0-60
ohm load)
Zero and full scale adjustable from -99999
to +99999
12 bits (0.025% of full scale)
250V rms working, 2.3 kV rms per 1 min test |
Dual
Contact Relay Outputs (optional) |
Relay
Type
Load Rating
Isolation |
Form
C
8A at 250 Vac or 24 Vdc
250V rms working, 2.3 kV rms per 1 min test |
Dual
Solid State Relay Outputs
(optional) |
Relay
Type
Load Rating
Isolation |
SPST,
normally open, Form A
120 mA at 130 Vac or 170 Vdc, 28 ohms series
resistance.
250V rms working, 2.3 kV rms per 1 min test |
Serial
Data I/O (optional) |
Board
Selections
Protocols
Data Rates
Digital Addresses
Isolation |
RS232,
RS485, Modbus RS485
Modbus RTU, Modbus ASCII, simpler Laurel ASCII
300 to 19200 bps
247 (Modbus), 31 (Laurel ASCII),
250V rms working, 2.3 kV rms per 1 min test |
Signal
Connections |
|

|
Environmental |
Operating
Temperature
Storage Temperature
Relative Humidity
Protection |
0°C
to 60°C
-40°C to 85°C
95% at 40°C, non-condensing
NEMA-4X (IP-65) when panel mounted |
|
Click
to Order DC Voltage or Current Input
Transmitter
|
|

|
|
Using
Laureate Meters and Counters to Instrument
an AC Line
|
| |
Why
Measure AC Power?
Many
AC loads, such as electrical motors,
will only operate reliably if the AC
line voltage and frequency are within
specified tolerances. Otherwise permanent
damage to expensive plant equipment
may occur.
Motor generators and UPS systems
will only operate reliably with the
load for which they are rated. Drops
in line voltage or frequency may indicate
an excessive load and the possibility
of equipment damage.
Laureate
meters and counters are low-cost means
to instrument AC power lines with great
accuracy:
-
AC
RMS Voltmeter. Full-scale
ranges of interest are 200.00 V with
10 mV resolution and 600.0 V with
100 mV resolution. True RMS capability
allows the display of RMS voltage
for non-sinusoidal waveshapes, such
as square waves from a UPS.
-
AC
RMS Ammeter. A built-in
5 A range can be used to display currents
up to 5.000 A with 10 mA resolution,
or to accept the output of 5 A current
transformers. The 200.00 mV range
can be used with external current
shunts. With either transformers or
shunts, scaling to the input current
is easily accomplished via the meter's
front panel pushbutton switches.
-
Frequency
Meter. Inverse period is used
to determine AC line frequency to
six-figure accuracy (60.0000 or 50.0000)
in a few line cycles plus 30 ms.
-
Phase
Angle Meter.
Two signals with identical
periods are applied to Channels A
and B of the Laureate phase angle
meter. A display from -180º to +180º
is obtained by timing the rising edge
of one channel and the falling edge
of the other channel. A resolution
of 1º, 0.1º or 0.01º is selectable.
Accuracy is .01% up to 100 Hz, .1%
at 1 kHz, and 1% at 10 kHz.
|
 |
|
Using
Laureate Meters to Synchronize Two Motor
Generators
|
Successful
synchronization of two motor generators
requires that the voltage outputs of
the generators be close to each other,
that the two frequencies be identical,
and that the voltage waveshapes be in
phase.
-
The
two voltages can
be measured by two Laureate AC RMS
Voltmeters, which offer 200.00 V
and 600.0 V ranges. Or a single
meter can be multiplexed by using
an external toggle switch.
-
The
two frequencies
can be measured to six-figure accuracy
by a single Laureate
Dual Channel Counter, where
each channel monitors a generator.
The two AC neutrals must be tied
to meter ground. Pressing a front-panel
key toggles the reading between
the channels.
-
Phase
angle
can be measured using the Laureate
Phase Meter.
|
|