Laurel Electronics
provides digital panel meters / controllers, totalizers, counters,
loop-powered meters, temperature meters, for all types of
transducers or process indication & control. |
|
|
|
|
Thermocouple
& RTD Temperature 4-20 mA
Current Transmitter
|

|
|
|
Click
to Order Thermocouple & RTD Temprrature
|
|
Features |
Input
for thermocouple types J, K, T, E, N, R, S. |
Input
for 100 ohm platinum RTDs with DIN and ANSI curves. |
2,
3 or 4-wire RTD connection with lead resistance
compensation. |
Upscale
or downscale open sensor indication. |
User
selectable spans from entire TC or RTD range down to
15.0°
|
2,
20, 200 mA and 5A DC current ranges. |
All
ranges factory calibrated. |
Isolated
4-20 mA or 0-10V isolated transmitter outputs,
selectable.. |
Output
resolution: 0.025% of span (12 bits). |
Output
update rate: to 60/sec. |
DIN
rail mount package only 22.5 mm thick.
|
Powered
by AC or DC. |
Detachable
screw-clamp connectors. |
|
Optional
dual solid state relays for alarm or control.
|
|
|
|
Description
|
|
Laureate™
4-20 mA transmitters with the temperature signal
conditioner board provide a linearized, highly
accurate, stable and repeatable transmitter output
for multiple thermocouple types and 100 Ohm platinum
RTDs. The meter accepts the outputs of types J, K,
T, E, N, R and S thermocouples, plus 100 ohm
platinum RTD’s with DIN alpha of 0.00385 and ANSI
alpha of 0.003925. The thermocouple or RTD and
temperature range, specified in °C or °F, are
user-selectable. The temperature range can be as
wide as the entire span of the thermocouple or RTD
type, or as narrow as 150 counts (such as 15.0°),
limited only by considerations of electrical noise
and digital filtering time constants.
Cold
junction compensation automatically corrects for
temperature variations at the thermocouple reference
junction at the transmitters. Open sensor indication
is standard and may be set up to indicate either
upscale or downscale. RTD excitation is provided by
the transmitter. RTD connections can be of the 2-,
3- or 4-wire type. For 3- and 4-wire connections,
the transmitter automatically compensates for lead
resistance of the sensor.
All
ranges for all temperature sensor types are
digitally calibrated at the factory. This eliminates
the need for field calibration or drift caused by
potentiometers found in non-microcomputer based
devices.
All
Laureate analog input meters and transmitters allow
exceptionally fast read rates. Concurrent Slope (Pat
5,262,780) is a method of analog-to-digital
conversion that allows up to 60 conversions per
second while integrating the input over a full power
cycle. Fast read rates provide true readings and
fast response for PID control applications and for
peak capture.
The
transmitters are housed in a DIN rail case that is
only 22.5 mm (0.89") thick. Signal connections
are via detachable screw-clamp plugs.
In
addition to the 4-20 mA output that would typically
be used for signal transmission in an industrial
environment, a 0-10V analog output is selectable.
Either selection provides 12-bit (0.025%) resolution
of output span and is ultra-linear, with the analog
output tracking the reading that would be
transmitted digitally.
Output isolation from
signal and power grounds is provided by a separate
on-board transmitter power supply, thereby
eliminating potential problems caused by ground
loops. The supply can an drive 20 mA into a 500 ohm
(or lower) load for 10V compliance, or 10V into 5K
ohm (or higher) load for 2 mA compliance.
Transmitter
programming is via a three-terminal RS-232 port
using Laurel's PC-based Instrument
Setup Software. This software can be downloaded
from this website at no charge. The required
transmitter-to-PC interface cable is available from
Laurel (P/N CBL03). |
|
Click
to Order Thermocouple & RTD Temprrature
|
|
Specifications- Laureate
4-20 mA Transmitters, Thermocouple or RTD Input
(Click on links in previous section
for details by signal type) Thermocouple
Input
|
| TC
Type |
Range |
Conformity
Error |
| J |
-210°C
to +760°C
-347°F to +1400°F |
0.09°C
0.16°F |
| K |
-244°C
to +1372°C
-408°F to +2501°F |
0.1°C
0.17°F |
| T |
0°C
to +400°C
-257°C to 0°C
+32°F to 752°F
-430°F to +32°F |
0.03°C
0.2°C
0.05°F
0.36°F |
| E |
-240°C
to +1000°C
-400°F to +1830°F |
0.18°C
0.32°F |
| N |
-245°C
to +1300°C
-410°F to +2370°F |
0.10°C
0.17°F |
| R |
-45°C
to +1768°C
-49°F to +3214°F |
0.17°C
0.31°F |
| S |
-46°C
to +1768°C
-51°F to +3213°F |
0.12°C
0.22°F |
|
Applicable
to all thermocouple types
|
Calibration
Input resistance
Input current
Max lead resistance
Span tempco
Reference junction tempco
Span tempco
Over-voltage protection
NMR at 50/60 Hz
CMR, DC-60 Hz
CMV, DC-60 Hz
Open sensor indication |
NIST
Monograph 125 (IPTS-68)
1 Gohm
100 pA
1 Gohm max for rated accuracy
±0.003% of reading/ºC
±0.02 deg/deg
±0.003% of reading/ºC
125 Vac
80 dB plus selectable digital filter from 80 ms
to 9.6 s time constant
120 dB with 500 W imbalance
250 Vac from power and earth grounds
0 mA or > 20mA output, selectable
|
Pt 100 RTD
Input
| RTD
Alpha |
Range |
Conformity
Error |
DIN
.00385 |
-202°C
to +850°C
-331°F to +1562°F |
0.03°C
0.05°F |
ANSI
.003925 |
-202°C
to +631°C
-331°F to +1168°F |
0.04°C
0.07°F |
|
Applicable
to all RTD types
|
Calibration,
DIN
Calibration ANSI
Configuration
Excitation current
Span tempco
Zero tempco
Sensor lead resistance
tempco per conductor
Over-voltage protection
Open sensor indication |
IEC
751 (IPTS-68)
NIST Monograph 126
2, 3 or 4-wire connection
0.2 mA
±0.003% of reading/ºC
±0.03 deg/deg
2-wire, 10 mdeg/W/deg up to 10 W
3 & 4-wire, 10 mdeg/W/deg up to 100 W
125 Vac
0 mA or > 20mA output, selectable |
Thermocouple
& RTD
| Analog
Output |
Output
Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation
Update Rate, Max |
4-20
mA or 0-10 Vdc (selectable)
10V ( 0-500 ohm load )
2 mA ( 5 kOhm load )
12 bits (4,096 steps)
±0.05% of output span
250V rms working, 2.3 kV rms per 1 minute test
50/sec at 50 Hz, 60/sec at 60 Hz. |
| Dual
Relay Output
(optional) |
Relay
Type
Load rating |
Two
solid state relays, SPST, normally open, Form A
120 mA at 130 Vac or 170 Vdc, 28 ohms series
resistance. |
| Power
Input |
Standard
power
Low power option
Frequency
Power Isolation |
95-240V
AC ±10% or 90-300V DC
12-30V AC or 10-48V DC
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test. |
| Mechanical |
Case
Dimensions
Case Mounting
Electrical Connections |
120
x 101 x 22.5 mm
35 mm rail per DIN EN 50022
Detachable screw terminal connectors |
| Environmental |
Operating
Temperature
Storage Temperature
Relative Humidity |
0°C
to 70°C
-40°C to 85°C
95% at 40°C, non-condensing |
Click
to Order Thermocouple & RTD Temprrature
|
|
Pinout
Laureate 4-20 mA
Thermocouple Transmitter
(shown with optional
dual relay output) |
|

Thermocouple
Transmitter Connection
RTD
Connections with Excitation & Lead
Compensation
|
|
The
Laureate temperature transmitter
allows 2-, 3- and 4-wire RTD
hookup to the J5 connector. The
transmitter applies an excitation
current of 0.2 mA, which it
monitors to make ratiometric
corrections for excitation supply
variations.
In
2-wire hookup, the transmitter
senses the voltage drop across the
100 ohm RTD and both lead wires.
The effect of the lead wires can
be measured and subtracted by
shorting out the RTD during
transmitter setup.
In
3- and 4-wire hookup, the
transmitter senses the voltage
drop across the 100 ohm RTD and
both lead wires as well as the
voltage drop across the RTD and
one lead wire. This allows the
transmitter to determine the
effect of one lead wire and
mathematically subtract the effect
of both lead wires.
|
|
|
|
|
Operation
as a Fast ON/OFF Controller or Supervisory
Monitor
With
the optional dual solid state relay output
option, which has a typical
response time of only 17 ms, Laureate
temperature meters and transmitters can
serve as extremely fast and accurate ON/OFF
controllers for closed-loop temperature
control. They can
also serve as supervisory process monitors
and provide alarms or shutoffs when
processes exceed normal limits.
Multiple
setpoint operating modes are individually
selectable for each relay, as explained in
the dual-setpoint
controller page. Relay duty cycles and
chatter can be minimized with programmable
hysteresis and time delays. A band
deviation operating mode can be selected
for each relay, where an alarm is
generated whenever the reading is a
selected number of counts above or below
the setpoint. The relay modes have to be
non-latching, since 4-20 mA temperature
transmitters do not offer external reset.
|
|
Strain Gauge Transmitter
|
|

|

|
|
Externally
Powered 4-Wire Process Transmitter
|
2-Wire
Process Transmitter
|
|
Click